Alarms

This page explains the built-in alarms, the three kinds of alarm rules and what you get when an alarm starts or ends.

Built-in alarms and alarm rules​

Three alarms work without any setup:

Built-in alarmStarts whenEnds when
Low batteryThe battery voltage drops below the low-battery threshold (battery-level, default 2.4 V)The voltage rises 0.3 V above the threshold
No dataA switched-on sensor or a 1-Wire probe stops delivering valuesValues arrive again
Wrong 1-Wire probeThe probe of a 1-Wire slot is missing and a probe of another type is connected that no free slot can take, see 1-Wire probesThe right probe is back or the slot is set up again

You can also create up to 16 alarm rules. Each rule watches one value of the STICKER board or of a 1-Wire probe. Several rules can watch the same value, for example a warning and a critical level. A rule stays inactive while its sensor or input is off.

Three kinds of rules​

Threshold rules​

A threshold rule watches a measured value such as temperature, humidity or an input voltage. The alarm starts when a reading leaves the range between the low and the high limit. It ends only when the reading is back inside by more than the hysteresis, so a value hovering at a limit does not start and end the alarm again and again.

Example: room temperature 5–30 °C with a hysteresis of 1 °C.

ReadingWhat happens
30.4 °CHigh alarm starts
29.5 °CAlarm continues, still above 29 °C
28.9 °CHigh alarm ends
4.6 °CLow alarm starts
6.2 °CLow alarm ends, above 6 °C

By default STICKER reads its sensors once per report interval (interval-report, default 15 min), so a threshold alarm can start up to 15 min late. To react faster, set a shorter sample interval (interval-sample, 5–3600 s).

State rules​

A state rule watches something that is on or off: a Hall switch, a digital input, PIR or accelerometer motion or the tilt alert of a MACHINE PROBE. You choose the state that raises the alarm and how long it must hold, up to 3600 s.

Example: a door contact on input A may open briefly. With a hold time of 5 s, the alarm starts once input A has been active for 5 s and ends as soon as the input is inactive again. If it becomes inactive sooner, nothing is sent.

Other variants fire once on a change or watch for motion or stillness, see Alarm rules.

Rate rules​

A rate rule watches a counter, such as a Hall switch, input, PIR or accelerometer count. You choose how many counts start the alarm and the length of the counting window, up to 3600 s.

Example: a flow meter on input A must not deliver 100 pulses within 15 s. The alarm starts as soon as 100 pulses are counted in one window, checked every 3 s. It stays one alarm while each following window reaches 100 pulses and ends after the first window with fewer.

When an alarm starts or ends​

  • Alarm report: STICKER collects alarm changes during a collection time (alarm-limit, default 10 s) after the first change and sends them in one alarm report, the message listing alarms that started or ended.
  • Extra telemetry: the first change also triggers a telemetry report (the regular measurement message) with the current values, within 10 s.
  • Alarm status: every telemetry report carries the alarm status, so your backend learns the state even when an alarm report is lost.
  • LED: a very short red flash every 3 s while any alarm is active and the device is Connected.
  • Buzzer: on the buzzer variant, the buzzer mode (alarm-buzzer-mode, default off) plays a short melody when an alarm starts, once or repeated until the last alarm ends.

Reliability​

  • No repeats by default: a lost alarm report is not sent again. With confirmed alarms switched on (radio-alarm-ack, default off), the network confirms each alarm report and STICKER repeats an unconfirmed one up to 3 times.
  • Offline: without a connection, STICKER holds the alarm report, collects up to 16 changes and sends them right after it joins the network again.
  • After a restart: STICKER starts without active alarms. Conditions that still hold, such as a temperature out of range, are reported again once the device is connected. Close the open alarms in your backend when the first telemetry report after a restart carries boot: true.

Setting up rules​

  • HARDWARIO Manager: Configuration → Alarms, see Alarm rules in the HARDWARIO Manager guide.
  • Downlink (a message from the network to the device): the set_param command with the rules alarm_0 to alarm_15, built for you by the Downlink commands generator.

A rule sent over a downlink or NFC works at once, but it survives a restart only after you save it. Saving restarts the device.

The temperature example as a downlink

Over a downlink, the temperature rule from the first example is the 18-byte value 0300000100000000a0400000f0410000803f. As JSON on fPort 85 (the LoRaWAN port for commands), written as rule 0 and saved:

{ "seq": 1, "command": "set_param", "set_param": { "alarms": { "alarm_0": "0300000100000000a0400000f0410000803f" }, "save": true } }

To write several rules, send them without save and set it on the last one only. If the device rejects one rule, it applies nothing from that message.