Configuration Reference

GLIDER stores configuration in non-volatile memory (NVS), so settings survive power cycles and reboots. You can change configuration through either console:

  • AT console: AT$CONFIG="<module>","<key>",<value>
  • RTT console (Zephyr shell): <module> config <key> <value>

After making changes, always save them to flash:

AT&W

This persists the new values and reboots the device. To wipe everything back to factory defaults:

AT&F

Listing configuration​

GoalAT commandShell command
List every moduleAT$CONFIG?config show
List one moduleAT$CONFIG="<module>"<module> config show
Read one keyAT$CONFIG="<module>","<key>"<module> config show <key>
Show full schemaAT$CONFIG=?-

The schema (AT$CONFIG=?) reports each key's type, range, default and a one-line description, useful for discovery.

Global app settings​

These keys apply to the whole device.

KeyTypeRangeDefaultDescription
interval-sampleint (s)5–360060How often the firmware reads sensors and evaluates alarms.
interval-sendint (s)30–86400300How often the firmware encodes a CBOR payload and uplinks it.
downlink-wdg-intervalint (s)0–1209600129600 (36 h)Downlink watchdog. If the cloud sends no downlink within this period, the device reboots. 0 disables the watchdog.

Example​

app config interval-sample 30
app config interval-send 120
AT&W

Digital inputs​

GLIDER has two galvanically isolated digital input channels (CH1 and CH2). Each channel can run in one of three modes:

ModeBehavior
disabledThe channel is powered off: no counting, no events.
counterSelected edges (rising / falling / both) increment counters. Counters are sent in every CBOR payload.
eventEach edge produces a timestamped event. Events are streamed in the next CBOR payload (up to 64 per channel, per send cycle).

Per-channel keys​

The same keys exist for both channels, prefixed with 1- (CH1) or 2- (CH2):

KeyTypeRangeDefaultDescription
<n>-modeenumdisabled / counter / eventdisabledChannel mode.
<n>-active-durationint (ms)0–60000100Minimum time the input must stay active (rising edge debounce).
<n>-inactive-durationint (ms)0–60000100Minimum time the input must stay inactive (falling edge debounce).
<n>-cooldown-timeint (ms)0–6000010Minimum time between two registered transitions.
<n>-counter-edgeenumrising / falling / bothbothWhich edges increment the counter (only used in counter mode).
<n>-event-typeenumactivation / deactivation / bothbothWhich transitions create events (only used in event mode).

Example - count pulses on CH1​

inputs config 1-mode counter
inputs config 1-counter-edge rising
inputs config 1-active-duration 5
inputs config 1-inactive-duration 5
AT&W

This counts every rising edge on CH1 as long as the input stays high for at least 5 ms (and low for at least 5 ms between pulses).

Thermometer slots (therm)​

Eight independent slots, one ROM code per slot. Empty slots are skipped in the cloud payload.

KeyTypeSizeDefaultDescription
1 … 8hex8 bytes0x00…DS18B20 ROM serial bound to that slot. 0x00… = empty.
tip

In practice you should not edit these by hand. Use therm scan --save to discover and bind sensors automatically. See External Temperature Sensors.

Alarms​

Up to 32 independent alarm rules can be configured. Each rule watches one thermometer slot and toggles between active and inactive based on a threshold with hysteresis:

  • The rule activates when temperature ≥ threshold.
  • The rule deactivates when temperature ≤ threshold − hysteresis.

Each transition is recorded in the alarm events buffer and uploaded with the next CBOR payload.

The same four keys exist for every rule, prefixed with <n>- (1-32):

KeyTypeRangeDefaultDescription
<n>-enabledbool-falseMaster switch for the rule. When false, the other keys for this rule are hidden.
<n>-thermint1–81Which thermometer slot the rule watches.
<n>-thresholdfloat (°C)−55–12550Activation threshold.
<n>-hysteresisfloat (°C)0–505Deactivation offset below the threshold.

Example - alarm on slot 1 if it exceeds 30 °C​

alarm config 1-enabled true
alarm config 1-therm 1
alarm config 1-threshold 30
alarm config 1-hysteresis 5
AT&W

When slot 1 reads ≥ 30 °C the firmware fires the alarm; it clears again when the reading drops to ≤ 25 °C.

Saving and resetting​

ActionCommand
Save and rebootAT&W
Factory reset (wipe everything)AT&F
Reboot without savingAT$REBOOT
caution

AT&F is destructive: every configured slot, alarm rule and interval is reset to factory defaults. There is no undo.