Schneider Electric IEM3XXX Series
Introduction
The iEM3200 series consists of compact, DIN-rail mounted energy meters designed for accurate and certified measurement of electrical energy in single-phase and three-phase systems. These meters are MID-compliant, making them suitable for both fiscal metering and cost allocation applications in residential, commercial, and light industrial installations.
This energy meter requires the use of an external sensor, such as a current transformer (CT), to measure current. The sensor must be selected based on the expected load and system configuration.
Power Installation
Example of Installation: Schneider Electric Energy Analyzer IEM3250
Schneider Electric Energy Analyzer IEM3250 | |
---|---|
Pin V1 | L1 |
Pin V2 | L2 |
Pin V3 | L3 |
Pin Vn | N |
In this case, it is also possible to connect the energy analyzer in single-phase mode, by wiring the neutral (N) to the Vn terminal and the phase (L) to terminal V1.
Sensor Installation
Example of Installation: Carlo Gavazzi AC Current Transformer CTD-1X 100 5A XXX
Electric Energy Analyzer IEM3250 | Carlo Gavazzi AC Current Transformer CTD-1X 100 5A XXX |
---|---|
Pin S1 | S1 (K) |
Pin S2 | S2 (L) |
Connection Diagram (IEM3250)
Modbus Communication
Example of Modbus Communication Installation: Schneider Electric Energy Analyzer IEM3250
Schneider Electric Energy Analyzer IEM3250 | CHESTER Modbus |
---|---|
Pin D0/- | Pin 6 (A−) |
Pin D1/+ | Pin 7 (B+) |
Pin 0V | Pin 1 (GND) |
Modbus communication (IEM3250)
Browsing and Configuration
-
▼
Arrow button- Navigation through the menu
- Increasing/Decreasing the value
-
OK
Select / Enter / Menu button -
ESC
Escape button
Modbus Communication and CT Ratio Configuration
- Press and hold the
OK
andESC
buttons until the password prompt appears. - Enter the password using the
▼
(Arrow button) button. (Default password for new meters is0010
.) - After entering the correct password, the configuration menu will appear.
- Use the
▼
(Arrow button) button to navigate to the menu item:Communication – Change?
. - Press the
OK
button to enter communication settings. - Configure the following parameters as needed:
• Address
• Baud Rate
• Parity
• Stop Bit • Stop Bit - Continue using the
▼
(Arrow button) button to scroll to the end of the menu. - At the
Exit Config
option, press theOK
button to confirm and save the settings.
Default Modbus Communication Configuration
Address | Baud Rate | Parity | Stop Bit |
---|---|---|---|
1 | 9.6k | None | 1 |
Example of CT Ratio Selection
Carlo Gavazzi AC Current Transformer CTD-1X 100 5A XXX
Model | CT Ratio |
---|---|
CTD-1X 100 5A XXX | 20 (100:5 → 20) |
The CT ratio is selected based on the maximum expected primary current. For example, if the system's maximum current is around 100 A, a 100:5 CT (20 CT) is chosen to step this down to 5 A for measurement devices.