Skip to main content

Carlo Gavazzi EM530

Carlo Gavazzi EM530

The EM530 is a three-phase energy meter from Carlo Gavazzi designed for use with external current transformers (CTs). It is suitable for monitoring higher-current circuits where direct connection is impractical.

Key Specifications

ParameterValue
Phases3-phase, 4-wire (+ neutral)
Current InputExternal CT: 5 A secondary
Voltage3× 230/400 V AC (50/60 Hz)
AccuracyClass 1 (active energy)
CommunicationModbus RTU (RS-485)
DisplayLCD
MountingDIN-rail
CertificationsCE

Measured Parameters

  • Active energy (kWh import/export)
  • Reactive energy (kVArh)
  • Active/reactive power per phase and total
  • Voltage, current, power factor, frequency

HARDWARIO Integration

The EM530 is used in industrial energy monitoring applications with HARDWARIO:

  • GAUGER: Reads three-phase power data via Modbus RTU and sends it to HARDWARIO Cloud for analysis.
  • Submetering: Monitoring energy usage per production line, machine group, or floor.

Resources