Modbus Registers

The counted data can be read out from the device through Modbus TCP. There are twelve holding registers in total. Two of them count each channel: one holds the number of activations, the other one the number of deactivations. A further register per channel holds the current state of the input.

AddressReading functionDescription
45301FC03Number of activations of the 1st input
45302FC03Number of activations of the 2nd input
45303FC03Number of activations of the 3rd input
45304FC03Number of activations of the 4th input
45305FC03Number of deactivations of the 1st input
45306FC03Number of deactivations of the 2nd input
45307FC03Number of deactivations of the 3rd input
45308FC03Number of deactivations of the 4th input
45309FC03State of the 1st input
45310FC03State of the 2nd input
45311FC03State of the 3rd input
45312FC03State of the 4th input